Pole selector
Selected pole
Still to choose: power supply, height, luminaires, pole top, wind speed, terrain.
- Top diameter
- Base diameter
- Wall
- Weight, galvanized
- Shape and steel
- Octagonal, S235, diameters across flats
- Base plate
- Anchor bolts
- Shaft to plate weld
- Utilisation in our table
- Top deflection, class 2 limit
Other poles that also pass
Pick one if you prefer a stiffer pole or a different wall. The drawing follows your pick.
No standard pole in our table carries this load. Send the selection and we propose a pole for it.
The pole data could not be loaded. Check the connection and try again.
The pole sizes on this page are pre-selected from a table calculated by Mir Group, based on EN 40-3-1, EN 40-3-3 and EN 1991-1-4, for standard octagonal S235 steel poles carrying our luminaires, using the wind class and terrain you choose. They are for preliminary selection and quotation only. They are not a structural design for a specific site. Wind speed, terrain, soil, foundation and local regulations must be confirmed by a qualified engineer for each project. Final dimensions are confirmed in our quotation.
Terrain categories
| Category | Terrain | z0 (m) | zmin (m) |
|---|---|---|---|
| 0 | Sea or coastal area exposed to the open sea | 0.003 | 1 |
| I | Lakes, or flat land with no obstacles | 0.01 | 1 |
| II | Low vegetation, isolated obstacles (open country) | 0.05 | 4 * |
| III | Suburbs, villages, industrial areas | 0.3 | 5 |
| IV | City centres, at least 15 % of the area built over 15 m | 1 | 10 |
* EN 1991-1-4 Table 4.1 gives 2 m for category II. The table uses 4 m, the value of our project calculations, which gives a higher wind load on the lowest 4 m of the pole and is on the safe side.
How the table is made
- Wind. The 3-second gust you choose is the value at 10 m above open, flat country. The table divides it by 1.45 to get the 10-minute mean wind that EN 1991-1-4 works with, then applies the terrain category you choose for the height of the pole. Winds come in 20 km/h steps from 100 to 200 km/h: for a value between two steps, the next step up is on the safe side.
- Loads. Wind on the shaft, the top unit and each arm luminaire from that wind and the terrain category, with the loads of EN 40-3-1 and the shape factors of EN 1991-1-4. The terrain roughness and minimum height come from the EU Joint Research Centre handbook on EN 1991-1-4 (JRC Handbook 3); category II uses the values of our project calculations, which are on the safe side.
- Checks. Bending and torsion of every section along the height and at the door opening (EN 40-3-3), with the second-order effect of the deflection, and the top deflection within the class 2 limit of EN 40-3-1: 0.06 × (height + half the arm length). Shaft, door section and arm tube are used to at most 90 % of their resistance. The base plate, its four anchor bolts and the weld are checked for the same loads, also to at most 90 %.
- Selection. All 3,840 combinations of power supply, height, luminaires, pole top, wind speed and terrain are solved in advance: top diameter 60 to 160 mm (80 mm or more under a top unit), wall 3 to 6 mm. The passing section with the lowest galvanized weight is shown first as Recommended, with up to two other passing sections that weigh more.
- Weights. The weights cover the shaft, base plate, four gussets and arm tubes; galvanized weight adds the minimum zinc coating of ISO 1461. Door frame and stiffener bars, cap, brackets and anchor bolts are not included. The all-in-one top units take a 60 or 76 mm spigot; the shaft top under a top unit is 80 mm or more, wider than the spigot, so the top fitting is agreed and priced in the quotation.
The foundation is not part of the table: it depends on the soil and is designed for each project.
Standards cited by name: EN 40-3-1, EN 40-3-3, EN 1991-1-4, ISO 1461. Free source: EU JRC, Eurocode 1 wind actions handbook. Table calculated on 2026-11-15.